8.0 DEFAULT JUMPER AND DIP SWITCH SETTINGS REV 02 AND GREATER ED2.0
Unless specified by the customer, the Low Energy and Under Voltage trip functions are disabled.
Input three is set for Auxiliary trip mode as opposed to the Protection Relay trip mode. The
Protection Relay mode has a lower switching threshold (12 V). See Illustration 13 in Appendix A
for Switch and Jumper locations. The following represents the functional Jumper and Dip Switch
settings which are the shipped configuration.
I1004 Energy failure auto trip and UV delay time
1234
Energy failure Auto Trip Enabled ON
Energy failure Auto Trip Disabled OFF
UV Disabled OFF OFF OFF
UV Delay 500 ms OFF ON OFF
UV Delay 1000 ms ON ON OFF
UV Delay 2000 ms OFF OFF ON
UV Delay 3000 ms ON OFF ON
UV Delay 4000 ms OFF ON ON
UV Delay 5000 ms ON ON ON
I1002 I1004
I1001 UV Threshold
123
220-240 VAC/VDC OFF OFF OFF
100-127 VAC/VDC ON OFF OFF
48-60 VAC/VDC OFF ON OFF
24-30 VAC/VDC OFF OFF ON
1
2
3
P
R
O
T
E
C
T
I
O
N
N
O
R
M
A
L
1
2
3
I1001
JP1019
Add Jumper for
33 Watt setting
I1002 UV Threshold Setting
1 2 3
Binary input used as Aux Open
OFF
Binary input 3 used as Safe Open
ON
Not Used leave in Off position
OFF
Undervoltage: CB Block in Open Position
OFF
Undervoltage: CB
ON
On filter card