Using PTP for synchronizing the MU
SAM600 VT SAM600 CT
SAM600 TS
IED
PTP
9-2
IEC17000040-1-en.vsdx
IEC17000040 V1 EN-US
Figure 87: Setting example with PTP synchronization
Settings on the local HMI under Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2:
HwSyncSrc: is not used as the SW-time and HW-time are connected with each
other due to PTP
SyncLostMode : set to Block to block protection functions if time
synchronization is lost or set to BlockOnLostUTC if the protection functions
are to be blocked when global common synchronization is lost
SyncAccLevel: can be set to 1μs since this corresponds to a maximum phase
angle error of 0.018 degrees at 50Hz
Settings on the local HMI under Main menu/Configuration/Communication/
Ethernet configuration/Access point/AP_X:
Operation: On
PTP: On
Section 15 1MRK 505 388-UEN B
Station communication
250 Busbar protection REB650 2.2 IEC
Application manual