3.9 ANALOG INPUTS
Static (Steady-State)
Group Number: 30
Static Frozen Group
Number: 31
Event Group Number: 32
Frozen Analog Input
Event Group Number: 33
Deadband Group
Number: 34
Capabilities
(leave tick-boxes blank if
this data type is not
supported)
Current Value
If configurable, list
methods
○ Variation 1 – 32-bit
with flag
Not Supported
○ Variation 2 – 16-bit
with flag
○ Variation 3 – 32-bit
with time-of-freeze
○ Variation 4 – 16-bit
with time-of-freeze
○ Variation 5 – 32-bit
without flag
○ Variation 6 – 16-bit
without flag
○ Variation 7 – Single-
precision, floating-point
with flag
○ Variation 8 – Double-
precision, floating-point
with flag
○ Based on point Index
(add column to table in
part 5)
3.9.8 Frozen Analog Input Event Variation reported when variation 0 requested or in response to Class
polls:
Note: The support for frozen analog input events can be determined remotely using protocol object Group
0 Variation 230.
Table continues on next page
Section 3 1MRK 511 419-UUS A
DNP3 protocol implementation
64 650 series 2.2 ANSI