Logic
Table 30. Configurable logic blocks
Logic block Quantity with update rate Range or value Accuracy
fast medium normal
LogicAND 90 90 100 - -
LogicOR 90 90 100 - -
LogicXOR 15 15 10 - -
LogicInverter 45 45 50 - -
LogicSRMemory 15 15 10 - -
LogicRSMemory 15 15 10 - -
LogicGate 15 15 10 - -
LogicTimer 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicPulseTimer 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicTimerSet 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms
LogicLoopDelay 15 15 10 (0.000–90000.000) s ± 0.5% ± 10 ms
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to integer
with Logic Node
4 4 8 - -
Integer to Boolean 16 4 4 8 - -
Integer to Boolean 16
with Logic Node
4 4 8 - -
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
42 ABB