Table 49. SLM – SPA/IEC 60870-5-103/DNP3 port
Quantity Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (3000ft/1000 m typically *)
Plastic fibre: 7 dB (80ft/25 m typically *)
Fibre diameter Glass fibre: 62.5/125 mm
Plastic fibre: 1 mm
*) depending on optical budget calculation
Table 50. Galvanic RS485 communication module
Quantity Range or value
Communication speed 2400–19200 bauds
External connectors RS-485 6-pole connector
Soft ground 2-pole connector
Table 51. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
Protocol IEC 61850-8-1
Communication speed 100 Base-FX
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2