Station communication
Table 44. IEC 61850-8-1 communication protocol
Function Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 608–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–19200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
Table 45. LON communication protocol
Function Value
Protocol LON
Communication speed 1.25 Mbit/s
Table 46. SPA communication protocol
Function
Value
Protocol SPA
Communication speed 300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number 1 to 899
Table 47. IEC60870-5-103 communication protocol
Function
Value
Protocol IEC 60870-5-103
Communication speed 9600, 19200 Bd
Table 48. SLM – LON port
Quantity
Range or value
Optical connector Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (10 m typically *)
Fibre diameter Glass fibre: 62.5/125 mm
Plastic fibre: 1 mm
*) depending on optical budget calculation
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2