ABB REC650 - Verifying the Back-Up Trip Mode; Verifying the Re-Trip Mode

ABB REC650
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Apply the fault condition, including start of CCRBRF, well above the set
current value. Measure time from START of CCRBRF.
2. Check the re-trip t1 and back-up trip times t2.
3. Disconnect AC and START input signals.
6.3.7.4 Verifying the re-trip mode
Choose the mode below, which corresponds to the actual case.
In the cases below it is assumed that FunctionMode = Current as set under Main
menu/Settings/IED Settings/Current/CCRBRF(50BF)/1:CCRBRF.
Checking the case without re-trip,
RetripMode
=
Retrip Off
1. Set RetripMode = Retrip Off.
2. Apply the fault condition, including start of CCRBRF, well above the set
current value.
3. Verify that no re-trip, but back-up trip is achieved after set time.
4. Disconnect AC and START input signals.
Checking the re-trip with current check,
RetripMode
=
CB Pos Check
1. Set RetripMode = CB Pos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set
current value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that no re-trip, and no back-up trip is obtained.
6. Disconnect AC and START input signals.
Checking re-trip without current check,
RetripMode
=
No CBPos Check
1. Set RetripMode = No CBPos Check.
2. Apply the fault condition, including start of CCRBRF, without any current.
3. Verify that re-trip is achieved after set time t1, and back-up trip after time t2.
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
6. Disconnect AC and START input signals.
6.3.7.5 Verifying the back-up trip mode
In the cases below it is assumed that FunctionMode = Current is selected.
1MRK 511 248-UEN - Section 6
Testing functionality
51
Commissioning Manual