4. Control
Synchrocheck, energizing check, and
synchronizing SESRSYN (25)
The Synchronizing function allows closing of
asynchronous networks at the correct moment
including the breaker closing time, which improves
the network stability.
Synchrocheck, energizing check, and synchronizing
(SESRSYN, 25) function checks that the voltages on
both sides of the circuit breaker are in synchronism,
or with at least one side dead to ensure that closing
can be done safely.
SESRSYN (25) function includes a built-in voltage
selection scheme for double bus and breaker-and-a-
half or ring busbar arrangements.
Manual closing as well as automatic reclosing can
be checked by the function and can have different
settings.
For systems which are running asynchronous a
synchronizing function is provided. The main
purpose of the synchronizing function is to provide
controlled closing of circuit breakers when two
asynchronous systems are going to be connected.
It is used for slip frequencies that are larger than
those for synchronism check and lower than a set
maximum level for the synchronizing function.
Autorecloser for 3-phase operation (79)
The autorecloser SMBRREC, 79 function provides
high-speed and/or delayed auto-reclosing for single
breaker applications.
Up to five three-phase reclosing attempts can be
included by parameter setting.
The autoreclosing function can be configured to co-
operate with a synchronism check function.
Apparatus control APC
The apparatus control functions are used for control
and supervision of circuit breakers, disconnectors
and grounding switches within a bay. Permission to
operate is given after evaluation of conditions from
other functions such as interlocking, synchronism
check, operator place selection and external or
internal blockings.
Apparatus control features:
Select-Execute principle to give high reliability
Selection function to prevent simultaneous
operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchrocheck
Operation counter
Suppression of Mid position
Two types of command models can be used:
Direct with normal security
SBO (Select-Before-Operate) with enhanced
security
Direct commands are received with no prior select
command. SBO commands are received with a
select command first and on successful selection, a
proceeding operate command.
In normal security, the command is processed and
the resulting position is not supervised. However
with enhanced security, the command is processed
and the resulting position is supervised.
Control operation can be performed from the local
HMI under authority control if so defined.
Bay control REC650 ANSI 1MRK 511 265-BUS B
Product version: 1.2
ABB 19

Other manuals for ABB REC650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REC650 and is the answer not in the manual?

ABB REC650 Specifications

General IconGeneral
Product TypeREC650
Voltage Supply100-240 V AC
Input Voltage24 - 240 V AC/DC
Communication ProtocolsIEC 61850, IEC 60870-5-103, Modbus, DNP3
InputsBinary inputs, analog inputs
OutputsBinary outputs
DisplayLCD
MountingPanel Mount
Protection FunctionsOvercurrent, Earth Fault, Distance Protection