Auxiliary AC and DC voltage
Table 3. Power supply
Description 600PSM02 600PSM03
V
n
48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50 and
60 Hz
110, 125, 220, 250 V DC
V
n
variation 80...120% of V
n
(38.4...150 V DC) 85...110% of V
n
(85...264 V AC)
80...120% of V
n
(88...300 V DC)
Maximum load of auxiliary voltage supply 35 W for DC
40 W for AC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption time in the
auxiliary DC voltage without resetting
the IED
50 ms at V
n
Binary inputs and outputs
Table 4. Binary inputs
Description Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.38 W
Threshold voltage 15...221 V DC (parametrizable in the range in steps of 1% of
the rated voltage)
Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/
R<40 ms, at V< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
Bay control REC650 ANSI 1MRK 511 265-BUS B
Product version: 1.2
ABB 65

Other manuals for ABB REC650

Related product manuals