Table 47. Autorecloser for 3-phase operation SMBRREC (79)
Function Range or value Accuracy
Number of autoreclosing shots 1 - 5 -
Autoreclosing open time:
shot 1 - t1 3Ph
(0.000-60.000) s
± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait time for sync (0.00-6000.00) s
Maximum trip pulse duration (0.000-60.000) s
Inhibit reset time (0.000-60.000) s
Reset time (0.00-6000.00) s
Minimum time CB must be closed before AR becomes ready for
autoreclosing cycle
(0.00-6000.00) s
CB check time before unsuccessful (0.00-6000.00) s
Wait for master release (0.00-6000.00) s
Wait time after close command before proceeding to next shot (0.000-60.000) s
Logic
Table 48. Tripping logic common 3-phase output SMPPTRC (94)
Function
Range or value Accuracy
Trip action 3-ph -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Bay control REC650 ANSI 1MRK 511 265-BUS B
Product version: 1.2
ABB 87