Table 60. Station battery supervision SPVNZBAT
Function Range or value Accuracy
Lower limit for the battery terminal
voltage
(60-140) % of Vbat ± 1.0% of set battery voltage
Reset ratio, lower limit <105 % -
Upper limit for the battery terminal
voltage
(60-140) % of Vbat ± 1.0% of set battery voltage
Reset ratio, upper limit >95 % -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 61. Insulation gas monitoring function SSIMG (63)
Function Range or value Accuracy
Pressure alarm 0.00-25.00 -
Pressure lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 62. Insulation liquid monitoring function SSIML(71)
Function
Range or value Accuracy
Alarm, oil level 0.00-25.00 -
Oil level lockout 0.00-25.00 -
Temperature alarm -40.00-200.00 -
Temperature lockout -40.00-200.00 -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 63. Circuit breaker condition monitoring SSCBR
Function
Range or value Accuracy
Alarm levels for open and close travel
time
(0-200) ms ± 0.5% ± 25 ms
Alarm levels for number of operations (0 - 9999) -
Setting of alarm for spring charging time (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure alarm (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure lockout (0.00-60.00) s ± 0.5% ± 25 ms