Completed with the optional synchrocheck func-
tion, voltage remant protection, and process bus
with sampled values of analog phase voltages, re-
lays with standard config. L ensure a safe intercon-
nection of two networks.
The standard configuration N provides the highest
functionality level of all standard configurations. It
is delivered as preconfigured, in the same way as
other 615 standard configurations. It is typically re-
configured when taken into use. This allows flexibil-
ity in standardizing one type of REF615. Depending
on the specific feeder application the appropriate
functionality can be selected and own configura-
tions can be created with the Application Configu-
ration tool in PCM600. Standard configuration N is
not designed for using all the available functional-
ity content in one relay at the same time. In order to
ensure the performance of the relay the user spe-
cific configuration load is verified with Application
Configuration tool of PCM600.
In addition to directional ground-fault protection,
one of these three functions can be ordered as an
option: admittance-based, harmonics-based or
wattmetric-based earth-fault protection. Admit-
tance- and wattmetric-based earth-fault protec-
tion functions are available for standard configura-
tions L and N. Harmonics-based earth-fault
protection is available for standard configurations
D, F, L and N. The admittance-based earth-fault
protection ensures a correct operation of the pro-
tection even though the connection status informa-
tion of the Petersen coil is missing. The standard
configurations L and N additionally offer multifre-
quency admittance-based ground-fault protection.
The configuration P provides the ideal functionality
for the implementation of Main-Tie-Main and Main-
Tie-Tie-Main Automatic Transfer Schemes. With Di-
rectional and non-directional overcurrent protec-
tion, for one breaker, and six voltage inputs for
undervoltage, overvoltage, negative-sequence volt-
age, and voltage remnant protection. The voltage
remnant protection is ideal for the implementation
Automatic Transfer schemes with motor loads con-
nected to the bus, where supervision is required to
prevent re-energizing the motors, before the power
is at an acceptable level. The configuration P is
completed with synchro-check functionality for the
implementation of Automatic Transfer Schemes
where the incoming sources would be paralleled
momentarily to increase reliability.
16 REF615 ANSI 5.0 FP1 FEEDER PROTECTION AND CONTROL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615 ANSI 5.0 FP1 and is the answer not in the manual?

ABB REF615 ANSI 5.0 FP1 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Binary OutputsUp to 8
Device TypeFeeder Protection Relay
Version5.0 FP1
Protection FunctionsOvercurrent, Earth Fault, Thermal overload, Under/Overvoltage, Under/Overfrequency
Communication ProtocolsIEC 61850, Modbus, DNP3
Auxiliary Supply Voltage110-250 V DC/AC
MountingFlush mounting
Operating Temperature Range-40 °C to +70 °C
Dimensions177 x 177 x 150 mm (H x W x D)
HousingPlastic
StandardIEC 60255
Input Voltage110-240 V AC/DC
EnclosureIP54