7. Measurements
The relay continuously measures the phase cur-
rents, the symmetrical components of the currents 
and the residual current. If the relay includes volt-
age measurements, it also measures the residual 
voltage, the phase voltages and the voltage se-
quence components. Depending on the standard 
configuration the relay additionally offers fre-
quency measurement. The relay also calculates the 
demand value of the current over a user-selectable, 
pre-set time frame, the thermal overload of the 
protected object, and the phase unbalance based 
on the ratio between the negative-sequence and 
positive-sequence current.
Furthermore, the relay offers three-phase power 
and energy measurement including power factor. 
The measured values can be accessed via the local 
HMI or remotely via the communication interface of 
the relay. The values can also be accessed locally or 
remotely using the Web HMI.
The relay is provided with a load profile recorder. 
The load profile feature stores the historical load 
data captured at a periodical time interval (demand 
interval). The records are in COMTRADE format.
8. Power quality
In the EN standards, power quality is defined 
through the characteristics of the supply voltage. 
Transients, short-duration and long-duration volt-
age variations and unbalance and waveform distor-
tions are the key characteristics describing power 
quality. The distortion monitoring functions are 
used for monitoring the current total demand dis-
tortion and the voltage total harmonic distortion.
Power quality monitoring is an essential service 
that utilities can provide for their industrial and key 
customers. A monitoring system can provide infor-
mation about system disturbances and their possi-
ble causes. It can also detect problem conditions 
throughout the system before they cause customer 
complaints, equipment malfunctions and even 
equipment damage or failure. Power quality prob-
lems are not limited to the utility side of the sys-
tem. In fact, the majority of power quality problems 
are localized within customer facilities. Thus, 
power quality monitoring is not only an effective 
customer service strategy but also a way to protect 
a utility's reputation for quality power and service.
The protection relay has the following power qual-
ity monitoring functions:
•  Voltage variation
•  Voltage unbalance
•  Current harmonics
•  Voltage harmonics
The voltage unbalance and voltage variation func-
tions are used for measuring short-duration volt-
age variations and monitoring voltage unbalance 
conditions in power transmission and distribution 
networks.
The voltage and current harmonics functions pro-
vide a method for monitoring the power quality by 
means of the current waveform distortion and volt-
age waveform distortion. The functions provides a 
short-term three-second average and a long-term 
demand for total demand distortion TDD and total 
harmonic distortion THD.
9. Fault location
The relay features an optional impedance-measur-
ing fault location function suitable for locating 
short-circuits in radial distribution systems. Earth 
faults can be located in effectively and low-resis-
tance earthed networks. Under circumstances 
where the fault current magnitude is at least of the 
same order of magnitude or higher than the load 
current, earth faults can also be located in isolated 
neutral distribution networks. The fault location 
function identifies the type of the fault and then 
calculates the distance to the fault point. An esti-
mate of the fault resistance value is also calculated. 
The estimate provides information about the pos-
sible fault cause and the accuracy of the estimated 
distance to the fault point.
10. Disturbance recorder
The relay is provided with a disturbance recorder 
featuring up to 12 analog and 64 binary signal chan-
nels. The analog channels can be set to record ei-
ther the waveform or the trend of the currents and 
voltages measured. 
The analog channels can be set to trigger the re-
cording function when the measured value falls be-
low or exceeds the set values. The binary signal 
channels can be set to start a recording either on 
the rising or the falling edge of the binary signal or 
on both.
By default, the binary channels are set to record ex-
ternal or internal relay signals, for example, the 
start or trip signals of the relay stages, or external 
blocking or control signals. Binary relay signals, 
such as protection start and trip signals, or an ex-
ternal relay control signal via a binary input, can be 
set to trigger the recording. Recorded information 
is stored in a non-volatile memory and can be up-
loaded for subsequent fault analysis.
26 REF615 ANSI 5.0 FP1 FEEDER PROTECTION AND CONTROL