EasyManuals Logo

ABB REF615 ANSI 5.0 FP1 User Manual

ABB REF615 ANSI 5.0 FP1
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
Figure 12. Application
example of busbar
differential protection
covering two zones using
standard configuration N
In the application example in Figure 12, single bus-
bar switchgear has been arranged into two bus
sections separated with bus coupler. Standard con-
figuration N is used with high-impedance differen-
tial protection for busbar and covering two zones
with two protection relays.
3
52
3
52
Δ
Y
52
Υ or Δ
Υ or Δ
3
REF615 Conf N
67P/51P/50P
50BF
67G/51G/50G
27
27R
25
AFD
3
3
REF615 Conf N
51P/50P
50BF
67/51G/50G
49F
AFD
REF615 Conf N
51P/50P
50BF
67/51G/50G
79
AFD
3
52
3
52
Δ
Y
52
Υ or Δ
Υ or Δ
3
3
REF615 Conf N
51P/50P
50BF
67/51G/50G
49F
AFD
REF615 Conf N
51P/50P
50BF
67/51G/50G
79
AFD
52
3
REF615 Conf P
67P/51P/50P
50BF
67N/51N/50N
27
27R
25
AFD
1
1
3 3
Cable
Overhead
line
Cable
Overhead
line
REF615 Conf N
67P/51P/50P
50BF
67G/51G/50G
27
27R
25
AFD
REF615 Conf N
87A
87B
87C
AFD
REF615 Conf N
87A
87B
87C
AFD
3
3
3
3
3
33
3
3
Stabilizing
varistor and
resistor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615 ANSI 5.0 FP1 and is the answer not in the manual?

ABB REF615 ANSI 5.0 FP1 Specifications

General IconGeneral
Rated Frequency50/60 Hz
Binary OutputsUp to 8
Device TypeFeeder Protection Relay
Version5.0 FP1
Protection FunctionsOvercurrent, Earth Fault, Thermal overload, Under/Overvoltage, Under/Overfrequency
Communication ProtocolsIEC 61850, Modbus, DNP3
Auxiliary Supply Voltage110-250 V DC/AC
MountingFlush mounting
Operating Temperature Range-40 °C to +70 °C
Dimensions177 x 177 x 150 mm (H x W x D)
HousingPlastic
StandardIEC 60255
Input Voltage110-240 V AC/DC
EnclosureIP54

Related product manuals