46 REF615 ANSI 5.0 FP1 FEEDER PROTECTION AND CONTROL
Table 41. Wattmetric-based earth-fault protection (WPWDE) main settings
Parameter Function Value (range) Step
Directional mode WPWDE


-
Current start value
WPWDE

n

Voltage start value WPWDE 
n
0.001
Power start value WPWDE 
n

Reference power WPWDE 
n

Characteristic angle WPWDE 
Time multiplier WPWDE  
Operating curve type

WPWDE
Definite or inverse time

Operate delay time
WPWDE  
Min operate current
WPWDE 
n

Min operate voltage
WPWDE 
n

Table 42. Transient/intermittent earth-fault protection (INTRPTEF)
Characteristic Value
Operation accuracy
Depending on the frequency of the measured current: f
n


Operate time accuracy 
Suppression of harmonics 
Table 43. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter Function Value (range) Step
Directional mode INTRPTEF



-
Operate delay time
INTRPTEF
 
Voltage start value INTRPTEF 
n

Operation mode INTRPTEF


-
Peak counter limit INTRPTEF 
Min operate current INTRPTEF 
n

Table 44. Harmonics-based earth-fault protection (HAEFPTOC)
Characteristic Value
Operation accuracy
Depending on the frequency of the measured current: f
n


n
Start time


Reset time 
Reset ratio 
Operate time accuracy in definite time mode 
Operate time accuracy in IDMT mode


Suppression of harmonics



n

n
-
surements
2) Includes the delay of the signal output contact

n
, Start value multiples in range of 2...20