56 REF615 ANSI 5.0 FP1 FEEDER PROTECTION AND CONTROL
Interconnection functions
Table 86. Directional reactive power undervoltage protection (DQPTUV )
Characteristic Value
Operation accuracy
Depending on the frequency of the measured current and voltage:
f
n


Power:

n
Voltage:

n
Start time


Reset time 
Reset ratio 
Suppression of harmonics 
n


n

2) Includes the delay of the signal output contact
Table 87. Directional reactive power undervoltage protection (DQPTUV) main settings
Parameter Function Value (range) Step
Voltage start value DQPTUV 
n

Operate delay time DQPTUV  
Min reactive power DQPTUV 
n

Min Ps Seq current DQPTUV 
n

Pwr sector reduction DQPTUV 
Table 88. Low-voltage ride-through protection (LVRTPTUV)
Characteristic Value
Operation accuracy
Depending on the frequency of the measured voltage:
f
n


n
Start time


Reset time Based on maximum value of Recovery time setting
Operate time accuracy 
Suppression of harmonics 
n

1) Tested for Number of Start phases = 1 out of 3, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact