EasyManua.ls Logo

ABB REG650 - Page 36

ABB REG650
73 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Type tests according to standards
Table 18. Electromagnetic compatibility tests
Description Type test value Reference
100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
Common mode 2.5 kV
Differential mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
Contact discharge 8 kV
Air discharge 15 kV
Radio frequency interference tests
Conducted, common mode 10 V (emf), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
Radiated, amplitude-modulated 20 V/m (rms), f=80...1000 MHz and f=1.4...2.7
GHz
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
Fast transient disturbance tests IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
Communication ports 4 kV
Other ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV line-to-earth
Other ports 2 kV line-to-earth, 1 kV line-to-line
Power supply 4 kV line-to-earth, 2 kV line-to-line
Power frequency (50 Hz) magnetic field IEC 61000-4-8, level 5
3 s 1000 A/m
Continuous 100 A/m
Pulse magnetic field immunity test 1000A/m IEC 61000–4–9, level 5
Damped oscillatory magnetic field 100A/m, 100 kHz and 1MHz IEC 6100–4–10, level 5
Power frequency immunity test IEC 60255-22-7, class A
IEC 61000-4-16
Common mode 300 V rms
Differential mode 150 V rms
Voltage dips and short interruptionsc on DC
power supply
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at power down
IEC 60255-11
IEC 61000-4-11
Generator protection REG650
1MRK 502 050-BEN B
Product version: 1.3
36 ABB

Other manuals for ABB REG650

Related product manuals