Table 63. Event recorder DRPRDRE
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on time
synchronizing
Table 64. Trip value recorder DRPRDRE
Function
Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
Table 65. Disturbance recorder DRPRDRE
Function
Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 96
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Table 66. Station battery supervision SPVNZBAT
Function
Range or value Accuracy
Lower limit for the battery terminal voltage (60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, lower limit <105 % -
Upper limit for the battery terminal voltage (60-140) % of Ubat ± 1.0% of set battery voltage
Reset ratio, upper limit >95 % -
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Battery rated voltage 20-250V -
Table 67. Insulation gas monitoring function SSIMG
Function
Range or value Accuracy
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Table 68. Insulation liquid monitoring function SSIML
Function
Range or value Accuracy
Timers (0.000-60.000) s ± 0.5% ± 110 ms
Generator protection REG650
1MRK 502 050-BEN B
Product version: 1.3
ABB 57