Table 69. Circuit breaker condition monitoring SSCBR
Function Range or value Accuracy
Alarm levels for open and close travel time (0-200) ms ± 0.5% ± 25 ms
Alarm levels for number of operations (0 - 9999) -
Setting of alarm for spring charging time (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure alarm (0.00-60.00) s ± 0.5% ± 25 ms
Time delay for gas pressure lockout (0.00-60.00) s ± 0.5% ± 25 ms
Metering
Table 70. Pulse counter PCGGIO
Function
Setting range Accuracy
Cycle time for report of counter
value
(1–3600) s -
Table 71. Function for energy calculation and demand handling ETPMMTR
Function
Range or value Accuracy
Energy metering MWh Export/Import, MVArh
Export/Import
Input from MMXU. No extra error at steady load
Generator protection REG650
1MRK 502 050-BEN B
Product version: 1.3
58 ABB