59
Preparing for test Chapter 10
Verifying settings by secondary
injection
Test/TestMode/DisturbReport
Table 3: Disturbance report settings
Operation Disturb-
Summary
Then the results are...
Off Off
• Disturbances are not stored.
• LED information is not displayed on the HMI and not
stored.
• No disturbance summary is scrolled on the HMI.
Off On
• Disturbances are not stored.
• LED information (yellow - start, red - trip) are displayed
on the local HMI but not stored in the terminal.
• Disturbance summary is scrolled automatically on the
local HMI for the two latest recorded disturbances, until
cleared.
• The information is not stored in the terminal.
On On or Off
• The disturbance report works as in normal mode.
• Disturbances are stored. Data can be read from the local
HMI, a front-connected PC, or SMS.- LED information
(yellow - start, red - trip) is stored.
• The disturbance summary is scrolled automatically on
the local HMI for the two latest recorded disturbances,
until cleared.
• All disturbance data that is stored during test mode
remains in the terminal when changing back to normal
mode.