EasyManua.ls Logo

ABB REL 505-C1 2.3 Series - Definite and Inverse Time-Delayed Residual Overcurrent Protection (TEF); Checking the Operate Values of the Current Measuring Elements

ABB REL 505-C1 2.3 Series
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66
Definite and inverse time-delayed
residual overcurrent protection (TEF)
Chapter 10
Verifying settings by secondary
injection
5 Definite and inverse time-delayed residual
overcurrent protection (TEF)
Prepare the terminal for verification of settings as outlined in section “Preparing for
test” in this chapter.
Normally, the test of the earth-fault overcurrent protection is made in conjunction with
the testing of the distance protection functions, using the same multiphase test-set. Ob-
serve that the polarising voltage is equal to 3Uo.
5.1 Checking the operate values of the
current measuring elements
Procedure
1. Set the logical input signals to logical 0 and note on the local
HMI that the TEF--TRIP and the TEF--TRSOTF signal is not ac-
tivated (= logical 0).
Values of the logical signals belonging to the time delayed residual
overcurrent protection are available under menu tree:
ServiceReport/Functions/EarthFault/TimeDelayEF
2. Set the polarising voltage to 2% of U
b
and the phase angle be-
tween voltage and current to 65°, the current lagging the volt-
age.
3. Check that the operate current of the forward directional ele-
ment is equal to the IN> Dir setting.
The IN> Dir function activates the TEF--STFW output.
4. Check with angles ϕ = 20° and 110° that the measuring ele-
ment operates when 3I
0
cos (65° - ϕ) >= IN> Dir.
5. Reverse the polarising voltage (ϕ = 180° + 65° = 245°) and
check that the operate current of the reverse directional ele-
ment is 0.6 · IN> Dir.
The function activates the TEF--STRV output.

Table of Contents

Related product manuals