Monitoring of DC analogue
measurements
Chapter 10
Verifying settings by secondary
injection
4. Check the operating monitoring levels by changing the mag-
nitude of input current and observing the operation of the cor-
responding output relays.
The output contact changes its state when the changes in the input
measuring quantity are higher than the set values RMAXAL, HI-
WARN, HIALARM, or lower than the set values LOWWARN,
LOWALARM, RMINAL.
5. Continue to test another function or complete the test by set-
ting the test mode to off.