1MDU07212-YN Rev. D Section 4
Protection and Control Function
REF601 / REJ601 / REM601 25
Application Manual
Table 12 Setting ranges for Auto-reclose function I <-> O, 79, continue
Parameter
Description
Range
Unit
Step
Default
Pulse tp
Auto reclose pulse time
0.2 … 20.0 [s]
s
0.1
0.2
Cycle t1
Dead time for first auto reclose
cycle
0.20 … 300.00 [s]
s
0.01
0.5
Cycle t2
Dead time for second auto
reclose cycle
0.20 … 300.00
s
0.01
0.5
Cycle t3
Dead time for third auto
reclose cycle
0.20 … 300.00
s
0.01
0.5
Cycle t4
Dead time for fourth auto
reclose cycle
0.20 … 300.00
s
0.01
0.5
Reclaim tr
Reclaim time
1 … 300
s
1
1
Block tb
Auto reclosure block time.
1 … 300
s
1
5
4.7.2.2 Configurable inputs to Auto-reclose function
Table 13: Configurable inputs to Auto-reclose function I <-> O, 79
Name
Type
Description
CB CLOS POS
BOOL
Circuit breaker closed position information
EXT TRIP
BOOL
External trip input
CB READY
BOOL
Circuit breaker ready information
4.7.2.3 Configurable outputs of Auto-reclose function
Table 14: Configurable Outputs to Auto-reclose function I <-> O, 79
Name
Type
Description
O→I CLOSE
BOOL
Closing command from auto reclosure
O→I IN
PROGRESS
BOOL
Reclosing cycle in progress, activated during
reclose time
FINAL TRIP
BOOL
Final trip from auto reclosure
O→I BLOCKED
BOOL
Auto reclosure blocked