EasyManua.ls Logo

ABB Relion 605 Series - Page 34

ABB Relion 605 Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 4 1MDU07212-YN Rev. D
Protection and Control Function
28 REF601 / REJ601 / REM601
Application Manual
The thermal model used during cooling condition for rotating machines is:
󰇡
󰇢

󰇡
󰇢



ϑ
1
= new value of thermal image
ϑ
0
= present value of thermal image
I = maximum value of measured phase currents
I
b
= base current (rated current/full load current defined by setting).
Δt = time interval between ϑ
0
and ϑ
1
τ
↓s
= Cooling time constant of standing objects
τ
↓r
= Cooling time constant of rotating objects (only REM601)
Emergency start function for motors:
An additionally configurable start emergency input (START_EMERG) is
provided. When the activated, the emergency mode is activated, which temporary
increase the thermal trip value ϑ
trip
by the setting ϑ
EM
in %. For function to remain
in emergency mode, it is required that START_EMERG remains active
continuously. As soon as the input is deactivated, trip value will restore back to
original setting. The activation and deactivation of input START_EMERG is
recorded as an event.
Block closing of CB
To prevent overheating of hotspots within a motor during startup, the restart could
be blocked if the actual thermal image is above by the setting of ϑ
startinhibit
. During
this condition the output to block closing of the CB (BLK_CLOSE) is activated.
When BLK_CLOSE is active closing of CB is not allowed by any means (i.e.
communication or HMI or binary input). The activation and deactivation of
BLK_CLOSE will be recorded as an event.
The thermal value of at the start of the function (i.e. at power on
of the IED is defined by a setting
Behavior of thermal image during power down condition of IED:
Condition arises where in the power supplied to the IED is interrupted. The user
could select four different behaviors / options to calculate the thermal level when
the power is restored. These options are selectable by the setting Mode ϑ
powerOFF
.
The thermal image along with time is stored every 60 sec. (and for option 1 also
the actual maximum phase current).

Table of Contents

Related product manuals