1MDU07212-YN Rev. D Section 5
Use of LHMI
REF601 / REJ601 / REM601 57
Application Manual
BO Configuration
BO behavior type: BO inversion
P Pulse type (200ms) S Self reset type - non inverted
L Lockout H Hold type I inverted
BO 1 2 3 4 5 6
Conf-P-P-P-S-P-P
Bin.Output123456
I> Start ------
Bin.Output123456
I>> Start ------
Bin.Output123456
I>>>Start ------
Bin.Output123456
I0> Start ------
Bin.Output123456
I0>>Start ------
Bin.Output123456
I> Trip XX--X-
Bin.Output123456
I>> Trip XX--X-
Bin.Output123456
I>>> Trip XX--X-
Bin.Output123456
I0> Trip XX---X
Bin.Output123456
I0>> Trip XX---X
Bin.Output123456
3Ith> Alm ------
Bin.Output123456
3Ith> Tr ------
Bin.Output123456
3Ith>BlkCl------
Bin.Output123456
I2tn< Mstr------
Bin.Output123456
CB Opn CmdXX----
Bin.Output123456
CB Cls Cmd--X---
Bin.Output123456
TCS Fault ------
Bin.Output123456
Unit Rdy ---X--
Bin.Output123456
I2tn< Trip------
Bin.Output123456
I2tn<BlkCl------
Bin.Output123456
I2/I1>Str ------
Bin.Output123456
I2/I1> Tr ------
Bin.Output123456
I2> Trip ------
Bin.Output123456
3I< Trip ------
Bin.Output123456
I2R> Trip ------
Bin.Output123456
BF Stage2 ------
Bin.Output123456
I2> Start ------
Bin.Output123456
3I< Start ------
Bin.Output123456
I2R>Start ------
Bin.Output123456
BF Stage1 ------
Bin.Output123456
BF RecTrip------
Bin.Output123456
0→I Close ------
Bin.Output123456
0→I InPro ------
Bin.Output123456
0→IFinalTr------
Bin.Output123456
0→IBlocked------
Bin.Output123456
Signal 1 ------
Bin.Output123456
Signal 2 ------
Bin.Output123456
Signal 3 ------

Table of Contents