Test point Reach Value Comments
5 X RFFwPE·tan (ArgLd) Only when RLdFw < RFFwPE
R RFFwPE
6 X -0.5·RLdFw·tan (ArgDir)
R 0.5·RLdFw
Table 19 is used together with figure 16.
X1
R
X
85%
1
3
5
2
6
4
50% RLdFw
ArgNegRes
0.5·RFFwPP
ArgLd
IEC09000735-3-en.vsd
ArgDir
60°
)/( phaseW
)/( phaseW
7
IEC09000735 V3 EN
Figure 17: Operating characteristic for phase selection function, forward
direction phase-to-phase faults
Table 20: Test points for phase-to-phase loops L1–L2 (Ohm/phase)
Test point
Reach Value Comments
1 X X1
R 0
2 X 0
R RLdFw When RLdFw < 0,5·RFFwPP
R 0,5·RFFwPP When RLdFw > 0,5·RFFwPP
3 X 0.85·X1 R=0.491·X1+0.5 RFFwPP
R 0.85·X1·1/tan(60°)+0.5 RFFwPP
4 X 0.85·X1 Can be limited by RFFwPP
R -0.85·X1·tan (AngNegRes-90°)
Table continues on next page
Section 10 1MRK 506 355-UEN A
Testing functionality by secondary injection
96 Line distance protection REL670 2.1 IEC
Commissioning manual