EasyManua.ls Logo

ABB Relion 670 Series REL670 - Verifying the Back-Up Trip Mode

ABB Relion 670 Series REL670
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Set RetripMode = CB Pos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set current
value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2
4. Apply the fault condition, including the start of CCRBRF, with the current
below the set current value.
5. Verify that no re-trip, and no back-up trip is obtained.
Checking re-trip without current check
1. Set RetripMode = No CBPos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set current
value.
3. Verify that re-trip is achieved after the set time t1, and the back-up trip after time
t2.
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
10.5.8.5 Verifying the back-up trip mode
In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1. Apply the fault condition, including start of CCRBRF, with phase current well
above set value IP>.
2. Interrupt the current, with a margin before back-up trip time, t2. It may be made
at issue of re-trip command.
3. Check that re-trip is achieved, if selected, but no back-up trip is obtained.
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests
above. In applicable cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose
the mode below, which corresponds to the actual case.
Checking the case
BuTripMode
=
1 out of 4
It is assumed that the earth-fault current setting IN> is below phase current setting
IP>.
1. Set BuTripMode = 1 out of 4.
2. Apply the fault condition, including start of CCRBRF, with one-phase current
below set IP> but above IN>. The residual earth-fault should then be above set
IN>.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4. Disconnect AC and START input signals.
1MRK 506 355-UEN A Section 10
Testing functionality by secondary injection
Line distance protection REL670 2.1 IEC 159
Commissioning manual

Table of Contents

Related product manuals