2 31
GUID-410C53C5-F990-4944-927D-3857E19B3AA9 V1 EN
Figure 71: Data set editor
1
Grid
2 Selection lists
3 List of data entries
1. Select an IED node in the IEDs navigation pane.
2. Click the Datasets tab in the editor pane.
3. Right-click the area containing data set names and select Insert new row.
4. Define the LN where the data set is to be placed (preselected LD0/LLN0 is
recommended) and the name for the new data set.
5. Click Append>> to add data items to the end of the data set or click Insert> to
add data items above the selected row in the data set entries list.
Reporting datasets can include status and measurement type of data. Also
configuration and setting values can be added to datasets in case required.
Above the data set entries list is shown how many attributes it is
possible to add to the data set and how many are already added.
1MRS757809 C Section 8
Engineering of event reporting with IET600
REC615 and RER615 105