Wait for GOOSE
Message
GOOSE Multicast MAC
Address and APPID Match?
GOOSE Message Received
Needs
Commissioning
?
GOOSE Receiver
Timeout
Target Data Value Is
Defaulted and Quality Set
To Invalid. Alarm Is Set
To TRUE
No Frames Received During 2xTAL
TRUE
Configuration
Revision
Mismatch?
FALSE
TRUE
Reset Receiver
Timer
Message Out of Order
or Dataset Mismatch?
FALSE
TRUE
Same State Number As
Previous Message?
Receiver Timeout
Counter +1
Needs
Commissioning
Counter +1
Configuration Revision
Mismatch Counter +1
Dataset Error
Counter +1
FALSE
FALSE
State or Sequence
Number Not As
Expected?
State or Sequence
Number Error Counter
+1
Frame Test or
Simulation field
Set?
Target Data Value and
Quality Are Updated
Accordingly
FALSE
Device In Test
Mode?
TRUE
TRUE
TRUE
Test Diagnostic
Counter +1
FALSE
Amount of data
entries same as in
previous msg?
TRUE
FALSE
Dataset Error
Counter +1
FALSE
TRUE
IEC 61850 Edition 2?
FALSE
TRUE
TRUE
TRUE
GUID-739488C5-3B0A-4126-A430-7E0FF1FBE505 V1 EN
Figure 35: Receiving GOOSE data in the protection relays
Section 5 1MRS757809 C
GOOSE
56 REC615 and RER615