EasyManua.ls Logo

ABB REQ650 - Page 54

ABB REQ650
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Auxiliary AC and DC voltage
Table 3. Power supply
Description 600PSM02 600PSM03
U
aux
nominal 48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50
and 60 Hz
110, 125, 220, 250 V DC
U
aux
variation 80...120% of U
n
(38.4...150 V DC) 85...110% of U
n
(85...264 V AC)
80...120% of U
n
(88...300 V DC)
Maximum load of auxiliary voltage
supply
35 W for DC
40 W for AC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 and 120 Hz)
Maximum interruption time in the
auxiliary DC voltage without resetting
the IED
50 ms at U
aux
Binary inputs and outputs
Table 4. Binary inputs
Description Value
Operating range Maximum input voltage 300 V DC
Rated voltage 24...250 V DC
Current drain 1.6...1.8 mA
Power consumption/input <0.38 W
Threshold voltage 15...221 V DC (parametrizable in the range in steps of 1% of
the rated voltage)
Table 5. Signal output and IRF output
IRF relay change over - type signal output relay
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time constant L/
R<40 ms, at U< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
Breaker protection REQ650 1MRK 505 283-BEN -
Product version: 1.2
54 ABB

Other manuals for ABB REQ650

Related product manuals