Table 19. Electromagnetic compatibility tests, continued
Description Type test value Reference
Voltage dips and short interruptionsc
on DC power supply
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at power
down
IEC 60255-11
IEC 61000-4-11
Voltage dips and interruptions on AC
power supply
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at power
down
IEC 60255–11
IEC 61000–4–11
Electromagnetic emission tests EN 55011, class A
IEC 60255-25
• Conducted, RF-emission (mains
terminal)
0.15...0.50 MHz < 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5...30 MHz < 73 dB(µV) quasi peak
< 60 dB(µV) average
• Radiated RF-emission
30...230 MHz < 40 dB(µV/m) quasi peak, measured
at 10 m distance
230...1000 MHz < 47 dB(µV/m) quasi peak, measured
at 10 m distance
Breaker protection REQ650 1MRK 505 283-BEN -
Product version: 1.2
60 ABB