Table 51. Autorecloser for 1/3-phase operation STBRREC
Function Range or value Accuracy
Number of autoreclosing shots 1-5 -
Autoreclosing open time: Shot 1 - t1
3Ph
Shot 1 - t1 1Ph
(0.000-60.000) s ± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait time for
sync
(0.00-6000.00) s
Open time extension for long trip time (0.000-60.000) s
Maximum trip pulse duration (0.000-60.000) s
Inhibit reset time (0.000-60.000) s
Reclaim time (0.00-6000.00) s
Minimum time CB must be closed
before AR becomes ready for
autoreclosing cycle
(0.00-6000.00) s
CB check time before unsuccessful (0.00-6000.00) s
Wait for master release (0.00-6000.00) s
Wait time after close command
before proceeding to next shot
(0.000-60.000) s
Logic
Table 52. Tripping logic common 3-phase output SMPPTRC
Function
Range or value Accuracy
Trip action 3-ph -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Table 53. Tripping logic phase segregated output SPTPTRC
Function
Range or value Accuracy
Trip action 3-Ph, 1/3-Ph -
Timers (0.000-60.000) s ± 0.5% ± 10 ms
Breaker protection REQ650 1MRK 505 283-BEN -
Product version: 1.2
76 ABB