Section 4 1MAC303209-MB C
Mounting
14 620 series
Installation Manual
Figure 4: Sealing screw
1 Sealing screw
2 Sealing wire and seal
4.3 Mounting the IED
4.3.1 Flush mounting the IED
All the mounting elements are integrated in the IED.
Requirements for installation:
• Panel cut-out of 9.76 x 6.38 inches (248 x 162 mm)
• Depth behind the panel 6.02 inches (153 mm)