ABB | SACE Emax 2
Ekip Touch - Settings
1 - Main settings
27 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Modules
The
Modules
menu provides various options:
Parameter Description Default
Local/Remote
The parameter defines the mode in which the parameters are written
in the unit:
•
Local
, parameter editing only via the display or service connector
•
Remote
, parameter editing only remotely (Ekip Com modules)
NOTES:
•
the Remote mode requires the presence of auxiliary power
supply and Ekip Com modules, otherwise it disables automatically
•
however, the Local/Remote parameter can still be edited in the
Remote mode
Local
Local bus
The parameter enables communication between the Trip unit and
modules installed via terminal box or outside the unit to be activated.
Correct communication between unit and modules is confirmed by:
• population of the
Modules
menu with all the modules connected
• Power Leds of the modules on and synchronized like the power led of
Ekip Touch
• absence of Local Bus alarm in the diagnosis bar
Off
Ekip Signalling
4K
Menu with the parameters of the Ekip Signalling 4K module, if present
Ekip Measuring Menu with the parameters of the module
Measurement
- Menu of every module connected and detected
Functions Access to the
LOCAL Switch On
and
RESET signaling
functions
Bluetooth Low Energy -
Connection security
Details of connection Security are available in manual 1SDH0013300R1002.