EasyManua.ls Logo

ABB SACE Emax 2 - Ekip Touch - Settings; Main Settings

ABB SACE Emax 2
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
Ekip Touch - Settings
1 - Main settings
26 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Ekip Touch - Settings
1 - Main settings
Foreword
All the following parameters are available either directly, or from the
Settings
menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
Consult manual 1SDH001330R1002 for any Main settings in the menu which are not described below
and for the Integrative settings (available by accessing the unit by means of a service connector via Ekip
Connect or by communication via system bus):
Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
Phase Sequence
Monitor time
Power Controller
Load Shedding
Network Analyzer
Datalogger
Dual Set
Functions
View
Maintenance
Programmable states
Filters
TAG Name, User data, Clients Page
LED Alive
Supplementary settings for commands, zone selectivity, Wizard
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration
The
Circuit breaker-Configuration
menu, allowing the presence of the
External neutral
sensor to be
activated, is available for the 3P CB.
Activation of the configuration with
External neutral
(3P + N) enables:
histograms of phase Ne in the
Histograms
page
neutral current measurements
submenu for configuring the Neutral protection (
Neutral Protection
)
neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection
In the earth
Circuit-breaker-Protections
menu of the LSIG version of Ekip Touch you can:
activate/deactivate the presence of external toroid S.G.R and relative Gext protection.
activate the presence of Rc Toroid and relative protection.
activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE:
Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
60 Hz.
NOTE:
the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.

Other manuals for ABB SACE Emax 2

Related product manuals