EasyManua.ls Logo

ABB SACE Emax E2.2 - 2 - Protections

ABB SACE Emax E2.2
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
24 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D Management operations | 4 - Environmental conditions
Mounting the fixed part of the
withdrawable circuit-breaker
Fasten the fixed part to a horizontal surface using four M8 x 25 screws for E2.2 and E4.2 fixed parts, and
using six M8 x 25 screws for E6.2 fixed parts. The screws are supplied by ABB. See Figure 56. Tighten the
screws with tightening torque = 21 Nm - 186 lb.in
OK
NO
Figure 56
WARNING! Emax E2.2-E4.2-E6.2 circuit breakers can only be installed in vertical
position
Lateral fixing (only for circuit-breakers to "IEC 60068-2-6 Test Fc" standards)
Further details about lateral fixing of fixed parts are available at http://www.abb.com/abblibrary/
DownloadCenter/, especially in the kit sheet 1SDH001000R0821.
Types of terminal
SACE Emax 2 circuit-breakers can be equipped with different combinations of terminals for the upper and lower part.
The following are the different types of terminal:
Figure 57 HR - Horizontal rear IEC
Figure 58 VR - Vertical rear IEC
Figure 59 SHR - Spread horizontal rear IEC (E2.2)
Figure 60 SVR - Spread vertical rear IEC (E2.2)
Continued on the next page

Other manuals for ABB SACE Emax E2.2

Related product manuals