EasyManua.ls Logo

ABB SACE Emax E2.2 - Page 226

ABB SACE Emax E2.2
302 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
External electronic accessories
5 - Ekip Com Modbus TCP
223 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Connections
The module must be assembled in the first vacant slot of the terminal box after
Ekip Supply
, either on the
circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 1SDM000091r0001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication
bus.
To connect the module to Ekip Touch, please consult document 1SDH001000r0514.
Power supply
Ekip Com Modbus TCP
is supplied directly by the
Ekip Supply
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence
of auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 132
LED Description
Power
Signals the on status and correct communication with Ekip Touch:
• Off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent
Link (1)
Indicates the communication state:
• Off: incorrect connection, signal absent
• on fixed: correct connection
Activity (2)
Indicates the communication state:
• off: no activity on the line
• flashing (activity on line present receiving and/or transmitting)