ABB | SACE Emax 2
Putting into service and maintenance
2 - Maintenance
266 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
2 - Maintenance
Safety standards
Comply with the following mandatory recommendations during maintenance work.
HAZARD! RISK OF ELECTRIC SHOCK! Risk of electric shock or accident.
WARNING! before proceeding with any maintenance operation, it is mandatory to:
Set the circuit-breaker to the open position and make sure that the springs of the
operating mechanism are discharged.
In the case of a withdrawable circuit-breaker, extract the circuit-breaker from the fixed
part (see the indication DISCONNECTED)
If work must be performed on fixed circuit-breakers or on fixed parts, disconnect the
power supply to the power circuit and auxiliary circuits and visibly ground the terminals
on both the supply side and load side.
Use adequate personal protection equipment, ensure that the apparatus is in a safe
condition and proceed in accordance with the Laws in force.
Skilled personnel
The maintenance operations must be carried out by Skilled Personnel:
skilled person, in the electrical field (IEV 195-04-01): person with sufficient training and experience to
enable him or her to perceive risks and avoid the dangers potentially created by electricity).
ABB declines all liability for damage to persons or property caused by failure to comply with the
instructions in this document.
Circuit-breaker life
The circuit-breakers SACE Emax 2, with or without opening or closing coils, can withstand the following
operating cycles if regularly serviced. For further information see chapter 3 - Environmental conditions
on page 7.
circuit-
breaker
IEC
60947
Inter
-
rupted
rated
current
Mechanical life
with regular main-
tenance
Electrical life
440 V 690 V 900 V 1000 V
1150 V /
1200 V
Frequency
of
operations/
hour
Iu (40°C)
[A]
No. of
operations
(x 1000)
Frequency of
operations/
hour
No. of operations (x 1000)
E1.2
</= 1000 20 60 8 8 - - - 30
1250 20 60 8 6,5 - - - 30
1600 20 60 8 6,5 - - - 30
1250L 20 60 3 1 - - - 30
E2.2
< 1250 25 60 15 15 2 0,5 - 30
1600 25 60 12 10 2 0,5 - 30
2000 25 60 10 8 2 0,5 - 30
2500 20 60 8 7 2 0,5 - 30
E4.2
< 2500 20 60 10 10 0,5 1 1 20
(1)
2500 20 60 8 8 0,5 1 1 20
(1)
3200 20 60 7 7 0,5 1 1 20
(1)
4000 15 60 5 4 0,5 1 1 20
(1)
E6.2
4000 12 60 4 4 1 - - 10
5000 12 60 3 2 1 - - 10
6300 12 60 2 2 1 - - 10
(1)
Only for 900V and 1150V circuit-breakers Operating sequences/hour = 10.
Continued on the next page