ABB | SACE Emax 2
External electronic accessories
10 - Ekip Com Hub
242 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
Continued from the previous page
The Remote FW update submenu enables the Firmware update function of the module to be managed;
the following parameters are available:
Parameter Description Default
Enable
Enables firmware update function of module to be remotely
activated/deactivated
OFF
Automatic
The parameter is available when Enable = On and allows the
automatic update mode to be activated (On): in the presence
of new Firmware, this latter is updated automatically. If the
parameter is Off, updating must be performed in the Manual
mode: in the presence of new Firmware, the message Ekip
Com Hub FW Update appears in the status bar and updating is
performed via the Manual command.
OFF (manual)
Start FW
update
This parameter is available when Enable= On, with Automatic=
Off configuration and when new Firmware is present (see
description above); allows the Firmware update of the module to
run
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the
module correctly:
Information Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
can be set via the menu in the event of a static IP
NOTE:
without a DHCP server, the module automatically adopts a random
IP address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set
of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of
several subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal
to ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter Description Default
CRL Enable
Allows the CRL (Certificate Revocation List) to be used to
ascertain whether the server certificate is valid
Clock update
hardening
enable
Enables control of the time reference transmitted by the SNTP
server
SNTP Server
Location
Enables the position of the SNTP server to be set in relation to
the network in which the module is installed
SNTP Time
zone
Defines the time zone to be used for synchronism +00:00
SNTP Daylight
Saving Time
Used to select whether daylight saving time is present (ON) or
not (OFF) in the country to which the synchronization time refers
OFF
Disable
Gratuitous ARP
Permits (Enabled ARP) the periodic generation of a Gratuitous
ARP message, used by Ekip Connect to rapidly find the modules
via Ethernet scan without knowing the IP address beforehand
ARP Enabled
Cloud data
send enable
Enables/disables the function that collects and transmits the
module data
OFF
JSON data
compression
Allows the compressed format of the JSON file sent to Cloud to
be selected (enable)
Disabled