10
Technical data Low-set stage I
0
>
Start current 0.2…2% x I
n
,
1…10% x I
n
or
5…50% x I
n
Start time, typically 75 ms
Operate time t>, definite time 0.05...1.00 s or
0.5...10.0 s
Reset time, typically 70 ms
Reset ratio, typically 0.96
Operate time accuracy ±2% of set value or ±40 ms
Operation accuracy
- within the setting range 0.2…2% x I
n
±5% of set value
- within the setting range 2…50% x I
n
±3% of set value
High-set stage I
0
>>
Start current 1…8% x I
n
&
∞
,infinite or
5…40% x I
n
&
∞, infinite or
25…200% x I
n
&
∞, infinite
Start time, typically 60 ms
Operate time t>> 0.05...1.00 s or
0.5...10.0 s
Reset time, typically 70 ms
Reset ratio, typically 0.96
Operate time accuracy ±2% of set value or ±40 ms
Operation accuracy ±3% of set value