13
Data Code Data Value
direction
Max. measured current or current V1 R 0…250% x I
n
measured at relay operation
Number of starts of stage I
0
> V2 R 0…255
Number of starts of stage I
0
>> V3 R 0…255
Duration of the latest start situation V4 R 0…100%
of stage I
0
>
Duration of the latest start situation V5 R 0…100%
of stage I
0
>>
Remote resetting of output relays V101 W 1 = output relays and opera-
and operation indicators tion indicators are reset
Remote resetting of output relays, V102 W 1 = output relays, operation
operation indicators and recorded data indicators and registers
(codes V1…V5) are reset
Remote adjustment of settings V150 R, W 0 = setting with setting knobs
S11…S15 alerted
1 = remote settings
S31…S35 alerted
Event mask V155 R, W 0…255, see chapter
"Event codes"
Manual/self reset of start and ope- V156 R, W 0…15, see chapter
ration indicators (switchgroup SG2) "Selector switches"
Opening of password for remote V160 W 1…999
setting of parameters
Changing or closing of password V161 W 0…999
for remote setting of parameters
Activation of self-supervision system V165 W 1 = self-supervision system
output is activated and
IRF indicator turns on in
about 5 seconds, where-
after the self-supervision
system resets and the
IRF indicator is switched
off
Internal fault code V169 R 0…255
Data communication address of V200 W 1…254
the relay module
Sofware version of module V205 R e.g. 069 B