EasyManua.ls Logo

ABB SwirlMaster FSS450 - 2.4 Zone 0, 1, 20, 21 type of protection intrinsically safe

ABB SwirlMaster FSS450
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SwirlMaster FSS430, FSS450 VortexMaster FSV430, FSV450 | CI/FSS/FSV430/450-EN Rev. D 11
Devices with LCD indicator, order code L2 (operation through the front glass)
Power supply, current / HART output, analog input
Temperature class T
amb
max. T
medium
max. U
max
I
max
P
i
max
T4 ≤ 60 °C 90 °C 30 V 100 mA 0.75 W
≤ 57 °C 180 °C
≤ 56 °C 280 °C
≤ 54 °C 400 °C
T4 ≤ 60 °C 90 °C 30 V 160 mA 1.0 W
≤ 57 °C 180 °C
≤ 56 °C 280 °C
≤ 54 °C 400 °C
T5 ≤ 56 °C 90 °C 30 V 100 mA 1.4 W
≤ 53 °C 180 °C
≤ 52 °C 280 °C
≤ 50 °C 400 °C
T6 ≤ 44 °C 90 °C 30 V 50 mA 0.4 W
≤ 41 °C 180 °C
≤ 40 °C 280 °C
≤ 38 °C 400 °C
Digital output
Temperature class T
amb
max. T
medium
max. U
max
I
max
P
i
max
T4 ≤ 60 °C 90 °C 30 V 30 mA 1.0 W
≤ 57 °C 180 °C
≤ 56 °C 280 °C
≤ 54 °C 400 °C
T4 ≤ 60 °C 90 °C 30 V 30 mA 1.0 W
≤ 57 °C 180 °C
≤ 56 °C 280 °C
≤ 54 °C 400 °C
T5 ≤ 56 °C 90 °C 30 V 30 mA 1.0 W
≤ 53 °C 180 °C
≤ 52 °C 280 °C
≤ 50 °C 400 °C
T6 ≤ 44 °C 90 °C 30 V 30 mA 1.0 W
≤ 41 °C 180 °C
≤ 40 °C 280 °C
≤ 38 °C 400 °C
Change from one to tw o columns