TPU2000/2000R Modbus/Modbus Plus Automation Guide
325
7/3 51P-1 Timedial/delay (dial 1-10, delay 0-10, *20)
8/1 50P-1 Curve Select byte (Type II)
8/2 50P-1 Pickup X byte (0.5-20, *10)
8/3 50P-1 Timedial/delay high (dial *10,delay *100)
9/1 50P-1 Timedial/delay low (dial 1-10, delay 0-9.99)
9/2 150P-1 Curve Select byte (Type II)
9/3 150P-1 Pickup X byte (0.5-20, *10)
10/1 150P-1 Time Delay high byte (0-9.99, *100)
10/2 150P-1 Time Delay low byte
10/3 46-1 Curve Select byte (Type I)
11/1 46-1 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
11/2 46-1 Timedial/delay (dial 1-10, delay 0-10,*20)
11/3 51N-1 Curve Select byte (Type I)
12/1 51N-1 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
12/2 51N-1 Timedial/delay (dial 1-10, delay 0-10,*20)
12/3 50N-1 Curve Select byte (Type II)
13/1 50N-1 Pickup X byte (0.5-20, *10)
13/2 50N-1 Timedial/delay high (dial *10,delay *100)
13/3 50N-1 Timedial/delay low (dial 1-10, delay 0-9.99)
14/1 150N-1 Curve Select byte (Type II)
14/2 150N-1 Pickup X byte (0.5-20, *10)
14/3 150N-1 Time Delay high byte (0-9.99, *100)
15/1 150N-1 Time Delay low byte
15/2 87T-2 Tap Amp byte (2-9 Amp *10, 0.4-1.8 Amp *50)
15/3 51P-2 Curve Select byte (Type I)
16/1 51P-2 Pickup Amp/OA (1-12 Amp *10, 0.2-2.4Amp *50)
16/2 51P-2 Timedial/delay (dial 1-10, delay 0-10, *20)
16/3 50P-2 Curve Select byte (Type II)
17/1 50P-2 Pickup X byte (0.5-20, *10)
17/2 50P-2 Timedial/delay high (dial *10,delay *100)
17/3 50P-2 Timedial/delay low (dial 1-10, delay 0-9.99)
18/1 150P-2 Curve Select byte (Type II)
18/2 150P-2 Pickup X byte (0.5-20, *10)
18/3 150P-2 Time Delay high byte (0-9.99, *100)
19/1 150P-2 Time Delay low byte
19/2 46-2 Curve Select byte (Type I)
19/3 46-2 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
20/1 46-2 Timedial/delay byte (dial 1-10, delay 0-10, *20)
20/2 51G-2 Curve Select byte (Type I)
20/3 51G-2 Pickup Amp byte (1-12A *10, 0.2-2.4A *50)
21/1 51G-2 Timedial/delay byte (dial 1-10, delay 0-10, *20)
21/2 50G-2 Curve Select byte (Type II)
21/3 50G-2 Pickup X byte (0.5-20, *10)
22/1 50G-2 Timedial/delay high (dial *10,delay *100)
22/2 50G-2 Timedial/delay low (dial 1-10, delay 0-9.99)
22/3 150G-2 Curve Select byte (Type II)
23/1 150G-2 Pickup X byte (0.5-20, *10)
23/2 150G-2 Time Delay high byte (0-9.99, *100)
23/3 150G-2 Time Delay low byte
24/1 Disturb-2 Pickup X byte (0.5-5, *10)
24/2 Level Detector-1 PickupX (0.5-20, *10, 201=Disable)
24/3 Level Detector-2 PickupX (0.5-20, *10, 201=Disable)
25/1 spare
25/2 spare
25/3 spare
26/1 Unit Configuration byte
bit 0 : neutral tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 1 : phase tap range Wdg1 (0=1-12A, 1=0.2-2.4A)
bit 2 : neutral tap range Wdg2 (0=1-12A, 1=0.2-2.4A)