TPU2000/2000R Modbus/Modbus Plus Automation Guide
51
Register
Address
Item Description
(Momentary)
00563: 51P-1D STATUS Winding 1 Phase Time Overcurrent Function Disabled Alarm
(Status)
00564: 51P-1D MOMENTARY Winding 1 Phase Time Overcurrent Function Disabled Alarm
(Momentary)
00565: 51P-2D STATUS Winding 2 Phase Time Overcurrent Function Disabled Alarm
(Status)
00566: 51P-2D MOMENTARY Winding 2 Phase Time Overcurrent Function Disabled Alarm
(Momentary)
00567: 51N-1D STATUS Winding 1 Neutral Time Overcurrent Function Disabled Alarm
(Status)
00568: 51N-1D MOMENTARY Winding 1 Neutral Time Overcurrent Function Disabled Alarm
(Momentary)
00569: 51N-2D STATUS Winding 2 Neutral Time Overcurrent Function Disabled Alarm
(Status)
00570: 51N-2D MOMENTARY Winding 2 Neutral Time Overcurrent Function Disabled Alarm
(Momentary)
00571: 50P-1D STATUS 1
st
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
00572: 50P-1D MOMENTARY 1
st
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00573: 50P-2D STATUS 1
st
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
00574: 50P-2D MOMENTARY 1
st
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00575: 50N-1D STATUS 1
st
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
00576: 50N-1D MOMENTARY 1
st
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00577: 50N-2D STATUS 1
st
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
00578: 50N-2D MOMENTARY 1
st
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00579: 150P-1D STATUS 2
nd
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
00580: 150P-1D MOMENTARY 2
nd
Winding 1 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00581: 150P-2D STATUS 2
nd
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Status)
00582: 150P-2D MOMENTARY 2
nd
Winding 2 Phase Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00583: 150N-1D STATUS 2
nd
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
00584: 150N-1D MOMENTARY 2
nd
Winding 1 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00585: 150N-2D STATUS 2
nd
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Status)
00586: 150N-2D MOMENTARY 2
nd
Winding 2 Neutral Instantaneous Overcurrent Function
Disabled Alarm (Momentary)
00587: 46-1D STATUS Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Status)
00588: 46-1D MOMENTARY Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Momentary)
00589: 46-2D STATUS Winding 1 Negative Sequence Time Overcurrent Function
Disabled Alarm (Status)

Table of Contents