EasyManua.ls Logo

ABB TTF300 - ATEX Zone 1 (20) Installation Hookup; ATEX Zone 2 and Zone 22 Installation

ABB TTF300
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TTH300, TTF300 TEMPERATURE TRANSMITTER | SM/TTX300/SIL-EN REV. E 13
Assumptions
The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis:
Failure rates are constant, wear out mechanisms are not included.
Propagation of failures is not relevant.
Failures during parameterization are not considered.
The device is locked / protected against unintended operation/modification.
The HART protocol is only used for setup and diagnostics purposes, not during normal operation.
The device is installed per manufacturer’s instructions.
The correct parameterization is checked be the end user.
Sufficient tests are performed prior to shipment to verify the absence of vendor and / or manufacturing defects that prevent
proper operation of specified functionality to product specifications or cause operation different from the design analyzed.
External power supply failure rates are not included.
As the optional display / control unit can interfere with the transmitter, the contribution to the dangerous undetected failure
rate was considered.
The worst case internal fault detection time is 2 minutes. Depending on the application, this interval needs to be considered
directly in the SIL verification.
Only the current output 4 to 20 mA is used for safety applications.
The application program in the safety logic solver is configured according to NAMUR NE43 to detect under-range low alarm
and over-range high alarm and does not automatically trip on these states; therefore, these failures have been classified as
dangerous detected failures.
Materials are compatible with process conditions.
The measurement / application limits are considered.
Short circuit and lead breakage detection are activated.
The minimum supply voltage used for the failure rate calculation is 15 VDC.
Diagnostics
The device's diagnostics setup meets the declared safety requirements in supporting the following runtime error detections:
Sensor configuration RTD: wire break and short circuit
Sensor configuration thermocouple: wire break
Several electrical part failures
• AD-converter error
Internal Power Supply error
Internal communication error
Program and Microcontroller supervision through watchdog
Sensor limit range alarm (upper and lower limits)
Flash ROM CRC16 error
• EEPROM CRC16 error
RAM Physical – Pattern Test error
RAM CRC16 data error
Drift error detection if configured and verified for the final dual redundant sensor assembly

Other manuals for ABB TTF300

Related product manuals