Brief operating instructions
42/18-64-4 EN Brief operating instructions b
Commissioning
1. Turn on the air supply to the positioner.
2. Apply the 4...20 mA analog input signal to the positioner.
3. Check for proper mounting:
- Press and hold
MODE
.
- Additionally briefly press or until mode 1.3 (manual adjustment within the sensor
range) is displayed.
-Release
MODE
.
- Press or to move the actuator to its mechanical limit stops in both directions, and
note the values. The angle of rotation is indicated in degrees.
4. Switch to the configuration level:
- Press and hold and simultaneously.
- Additionally briefly press
ENTER
.
- Wait until the countdown from 3 to 0 is completed.
- Release and .
The device will automatically go to parameter group P1.
5. Select the actuator type (parameter P1); select ROTARY or LINEAR using or .
6. Start Autoadjust:
- Press and hold
MODE
.
- Additionally briefly press ; until "P1.1" is indicated.
-Release
MODE
.
-Press
ENTER
and keep it pressed until the countdown is finished.
-Release
ENTER
.
Autoadjust is started.
- If the message "COMPLETE" is displayed to indicate successful Autoadjust, briefly
press
ENTER
to acknowledge.
It is also possible that Autoadjust is automatically cancelled due to troubles, and an
error message is displayed. See P 1.1 Autoadjust on page 53 for details.
Recommended positions of limit stops:
> -28° and < +28° for linear actuators
>-57° and < +57° for rotary actuators
Minimum angle: 25°
This step must be performed prior to Autoadjust (step 6).
Caution

Related product manuals