• Feed the cable through the connector and cut the cable to size
Ensure that the cable's radius of curvature is more than 4 times the diameter of the cable
• Prepare the cable respecting the following measurements.
N
L
Max 6 mm²
x:
8 mm
Ø10÷14mm
x
y
y:
30mm
L,N 25 mm
• Install the single wires (phase, neutral and ground) on the head of the
connector respecting the indications printed on each of the three connec-
tion terminals (tightening torque 0.8...1Nm)
• Close the connector and tighten the cable gland respecting the tighten-
ing torque (4+1Nm) in order to guarantee the IP65 protection level