7 - Operation
• Gogo Rel(Auto) (display text “Gogo Rel(Auto)”)
It allows you to enable the GoGo Rel mode with which the relay is activ-
ated (status: switched) to a specic congurable power input threshold.
Once this mode has been selected, the parameters for which the relay is
activated have to be set (status: switched) and the parameters for which
it is deactivated, in the dedicated submenu GoGo Cong:
- Pstart: Upper power threshold (this can be set from 30% to
90% of the nominal input power) for which the relay is activ-
ated (status: switched).
- Hyst OFF: Lower power threshold (this can be set from 30%
to 70% of the Pstart set) for which the relay returns to its rest
position.
- Min ON Time: Minimum time period in which the relay is ac-
tivated (status: switched) following the Pstart threshold being
exceeded by the input power.
- Min OFF Time: Minimum time period in which the relay
stays in its rest position after the input power has fallen below
the Hyst OFF threshold.
10. Stand Alone
This section of the menu is only available if the "Stand Alone" accessory
board has been installed and if the "Set Stand Alone" function has been
enabled from the service menu (Inverter>Settings>Service). Through
this section, it is possible to congure the operating mode of the "Stand
Alone" accessory board selecting from "None" and "Man 1": Using
"None" the board functions are disabled, while by selecting "Man1" they
will be enabled.