1.4. Weights and overall dimensions
Contactor VSC7
VSC12
VSC-S/G
VSC7/F VSC7/FN
VSC12/F
VSC-S/F
VSC7/P
VSC12/P - VSC12/PG
VSC-S/PG
VSC7/PN VSC7/PNG VSC12/PN
VSC12/PNG
VSC-S/PNG
Weight [Kg] 23 23 35
(1)
35
(1)
35
(1)
52
(1)
52
(1)
45
(1)
45
(1)
45
(1)
45
(1)
Overall
dimensions
[mm] H 371 424 494 598 532
636 636 653 653 653 653
[mm] W 350 350 466 466 466 531 531 350 350 350 350
[mm] D
215 215 622 623 702 657 657 673 673 673 673
(1)Withoutfuses
1.3. Characteristics
Contactor
Reference
IEC 62271-106
VSC7
VSC7/F (
1
)
VSC7/P (
1
)
VSC7/PN (
1
)
VSC7/FN
VSC12
VSC12/F (
1
)
VSC12/P (
1
)
VSC12/PN (
1
)
Reference VSC7/PNG (
1
) VSC12/PNG (
1
) VSC-S/G
VSC-S/F (
1
)
VSC-S/PG (
1
)
VSC-S/PNG (
1
)
GB/T
14808-2001
DL/T
593-2006
Rated voltage [kV] 4.1 7.2 12 4.1 7.2 12 12
Rated insulation voltage
Withstand voltage at 50 Hz [kV]
6.2 23 28 6.2
32 42 28(
3
)
Impulse withstand voltage
[kVbil] 6.2 60 75
6.2 60 75 75
Rated frequency [Hz] 4.3 50-60 50-60 4.3 50-60 50-60 50-60
Rated service current [A] 4.101
400 400 4.101 400 400 250
Short-time withstand current
Short-time withstand current for 1 s [A] 6.6 6,000 6,000 6,000 600
Short-time withstand current for 2 s [A] 6.6 4,000 4,000
Short-time withstand current for 4 s [A]
4,000 4,000
Short-time withstand current for 30 s [A] 6.6 2,500 2,500 6.6 2,500 2,500 2,500
Rated peak current [kA] 6.6 15 15 6.6 15 15 15
Rated values
Operations/hour(SCO-DCO) [Nr.] 4.102.4 1.200 1,200 4.102.2 1,200 1,200 1,200
Rated voltage of the voltage characteristics in category of use
(CategoryAC4)100closingoperations [kA] 6.102.4 4,000 4,000 6.102.4 4,000 4,000
(CategoryAC4)25openingoperations [kA] 6.102.5 4,000 4,000 6.102.5 4,000 4,000
Switching devices and auxiliary circuits
4.8,4.9
4.8,4.9
Feeder 1 24÷60 V dc basic
Feeder 2 24÷60 V dc full option
Feeder 3 110÷250 V dc/ac basic
Feeder 4 110÷250 V dc/ac full option
Normal current [A] 6.4.6.5 400 400 6.4,6.5 400 400 400
Mechanical life [Nr.] 6.101 1,000,000(
2
) 1,000,000(
2
) 6.101 1,000,000(
2
) 1,000,000(
2
) 200,000
Short-circuitbreakingcapacity(O-3min-CO-3min-CO) [A] 6.104 5,000 5,000 6.104 5,000 5,000 -
Short-circuitmakingcapacity(O-3min-CO-3min-CO) [A] 6.104 13,000 13,000 6.104 13,000 13,000 -
Opening time [ms] 35...60 35...60 35...60 35...60 35...60
Closing time [ms] 60...90 60...90 60...90 60...90 60...90
Tropicalisation IEC 721-2-1
(1)Itispossibletocombinecurrentlimitingfuseswithbreakingcapacityupto50kA(IEC62271-106-4.107)-Damageclassification“C”(IEC62271-106-4.107.3).
(2)Withreplacementofauxiliarycontactsevery250,000closing-openingoperations.
(3)42kVforfixedversionsandindedicatedUnigearswitchgear