EasyManuals Logo

ABB VD4 Installation And Operating Instructions

ABB VD4
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
MEDIUM VOLTAGE PRODUCTS
13
5.3.4 General specifications of fixed circuit breakers with lh lateral operating mechanisms for ABB UniSec switchgear (12-17.5-24 kV)
(
1
) for 12.08.20 and 17.08.20, versions with withstand voltage up to 42 kV are available
(
2
) rated duty breaking capacity 21 kA at 17.5 kV. Rated short-time withstand current 21 kA x 3 s
(
3
) rated short-time withstand current 25 kA x 2 s
(
4
) increase the indicated weight by 20 kg for circuit breakers with REF 601 devices and 3 current sensors
(
5
) “IEC” or “CEI 0-16” version. If the “CEI 0-16” is required, the circuit breaker is always supplied with 3 phase current sensors (Rogowsky coils) installed on the actual circuit breaker and with a
loose toroidal TA. In the “CEI 0-16” version, the REF 601 device opens the circuit breaker by means of the undervoltage release -MU
(
6
) the rated current of the REF 601 device must be set in the relay in accordance with the circuit breaker’s rated current
(
7
) for 12.08.20 and 17.08.20, versions with operating temperature up to -25 °C and storage temperature up to -40 °C are available
Circuit breaker VD4/L-SEC12 VD4/L-SEC17 VD4/L-SEC24
Standards   
  
Rated voltage Ur [kV]   
Rated insulation voltage Us [kV]   
  
) 
) 
Impulse withstand voltage Up [kV]   
Rated frequency fr [Hz]   
 Ir [A]         
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Isc [kA]       
      
   
) 
)  
    
 Ik [kA]       
      
   
) 
)  

) 
)  
) 
)
Making capacity Ip [kA]       
      
      
    
Sequence of operations   
Opening time [ms]   
Arcing time [ms]   
Total break-time [ms]   
Closing time [ms]   
Overall dimensions
(maximum)
H [mm]   
W [mm]   
D [mm]   
Pole center-distance P [mm]   
Weight (
) [kg]   

) 
) 
) 
)
Standardized dimensions table   
Wiring diagram    
Operating temperature C] 
) 
) 
)
Tropicalization   
Electromagnetic compatibility   
H
W
D

Other manuals for ABB VD4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB VD4 and is the answer not in the manual?

ABB VD4 Specifications

General IconGeneral
TypeVacuum Circuit Breaker
Rated VoltageUp to 36 kV
Rated Short-Circuit Breaking CurrentUp to 63 kA
Frequency50/60 Hz
StandardsIEC 62271-100
ApplicationMedium voltage power distribution
Rated Short-Time Withstand CurrentUp to 63 kA for 3 seconds
Mechanical LifeUp to 30, 000 operations
InstallationFixed / Withdrawable
Operating MechanismSpring-operated
Rated Current630 A / 800 A / 1250 A / 1600 A / 2000 A / 2500 A / 3150 A / 4000 A
Electrical LifeUp to 10, 000 operations at rated current
Control Voltage24 V DC, 48 V DC, 110 V DC, 220 V DC, 110 V AC, 230 V AC

Related product manuals